Identifying A Control Module In The Can Network
If the load on the CAN network is too high, this may be due to a control module sending faulty messages on the CAN network (known as a disruptive control module). The fault may also be due to an intermittent short-circuit to supply voltage or ground in one of the CAN cables. This results in the control modules on the CAN network starting to send faulty messages. The faults can occur without a diagnostic trouble code (DTC) being stored by the control modules. The voltage can be measured between the CAN cables in order to check the load on the CAN network.
- Measure the voltage between terminals #G14 (#14) and #G15 (#15). Average voltage must be approximately 0.5 V (0.4-0.6 V). If there is a fault in communication, the voltage reading will be approximately 0.7 V or higher.
In order to identify which control module is communicating incorrectly, cut the power supply to one control module at a time. Check the voltage in the CAN cables again. The easiest way to cut the power supply is to remove the fuse(s) for the relevant control module. Continue until the voltage between the CAN cables drops to approximately 0.5 V.
HINT: When the suspected control module has been identified, connect and disconnect the supply voltage to the control module a number of times to verify that the fault appears and disappears. Ignition off between each check.
The control module that is communicating incorrectly must be replaced.
Remedy as necessary.